This study focuses on the solid oxide fuel cell (SOFC) cogeneration system for commercial buildings. SOFCs are considered to be suitable for buildings with low thermal demand because of the high power generation efficiency. The objective of this study is to analyze the effects of SOFC installation into various commercial buildings from energy saving and economic aspects using optimization minimizing the system cost. Primary energy reduction rate was used as the indicator of the energy saving performance. The results showed that SOFCs are effective to reduce primary energy consumption for all the buildings analyzed in this study. Based on the analysis of the optimal installation, it is suggested that SOFCs economically perform better for the buildings such as hospitals, hotels and restaurants with hot water demand than for offices without hot water demand. Restaurants operating for 24 hours are expected to be a promising candidate of SOFC, which can accept the cost of SOFC as high as 1.05 million yen per kilowatt. Furthermore, sensitivity analysis on the effects of SOFC installation based on renewable energy levy showed that installation of SOFCs would be promoted strongly for buildings with high electricity demand.